What is the CPR
♦The selection of environments for infrastructure cabling must be made with due regard for CPR.
♦♦What is the CPR ?
♦Construction Product Regulation is a regulation issued by
the European Union and its purpose to :
♦Ensure the harmonization across Europe of the materials and achieve higher safety levels for fire and dangerous substances in materials used in construction
♦The CPR includes four classes that
directly apply to cables: B2, C, D and E.
These classes refer to combustible cables in ascending order of fire growth rate and heat release.
All of these cables also comply with the flame non-propagation
test in accordance with EN 60332-1-2.
♦B2ca : Very high fire protection self extinguishing, used for hospitals, Airports and fire exits in public buildings (High density of people).
♦Cca : high fire protection self extinguishing, used for public buildings, Hotels, schools and office buildings (Medium density of people).
♦Dca : Moderate fire protection limited emission, used as a minimum cable requirement for general installation depend on regions
♦Eca : Basic fire protection, used as a minimum cable requirement for general installation depend on regions.
♦♦Three additional classification levels have been established regarding:
♦The amount of smoke produced (s), Smoke Opacity
•s1: Little production and slow propagation of smoke
•s1a: S1 with visibility over 80%
•s1b: S1 with visibility over 60% and below 80%
•s2: Intermediate values of production and propagation of smoke
•s3: Neither s1 or s2
♦The particles released by the cable during combustion (d), Fall of droplets during combustion
•d0: No fall of droplets or flamed particles.
•d1: Fall of droplets and inflamed particles that persist for less than 10 seconds.
•d2: Neither d0 or d1.
♦The acidity – or toxicity – of the smoke (a), Smoke Acidity.
•a1: Low acidity, and its conductivity <2,5ms/mm y pH > 4.3)
•a2: Intermediate values of acid and its conductivity <10ms/mm y pH > 4.3)
•a3: Neither a1 or a2.
♦♦Why is LSZH no longer enough?
LSZH stands for Low Smoke Zero Halogen. It was originally designed to meet IEC standards: IEC60332 (Flame Spread), IEC60754 (Smoke Acidity) and IEC61034 (Smoke Emission). However, because the CPR applies additional criteria and testing procedures, simply buying any cable labelled as LSZH may not be enough to ensure it reaches the minimum standard.
In conclusion, CPR-rated cables are specifically designed for construction projects and are categorized into Euroclasses, which denote their fire performance. These Euroclasses represent a more rigorous standard than LSZH.
♦The Importance of Compliance :
1. Minimizing Property Damage: Fires can cause extensive damage to buildings and property. CPR-compliant cables can help minimize this damage, reducing repair and replacement costs.
2. Legal Requirement: CPR compliance is not optional, it's a legal requirement. Failure to comply can result in legal consequences and liabilities.
Quy định về Môi trường cho Cáp Hạ tầng
Việc lựa chọn môi trường cho cáp hạ tầng phải tuân thủ Quy định Sản phẩm Xây dựng (CPR).
CPR là gì?
CPR là quy định của Liên minh Châu Âu, nhằm:
Đảm bảo sự hài hòa hóa vật liệu xây dựng trên toàn Châu Âu.
Đạt được mức độ an toàn cao hơn về cháy và các chất nguy hiểm trong vật liệu xây dựng.
Các lớp CPR cho cáp
CPR bao gồm 4 lớp áp dụng trực tiếp cho cáp: B2, C, D và E. Các lớp này phân loại cáp dễ cháy theo tốc độ phát triển cháy và nhiệt phát ra.
Các lớp CPR
B2ca: Bảo vệ cháy cao, tự dập tắt, sử dụng cho bệnh viện, sân bay và lối thoát hiểm công cộng.
Cca: Bảo vệ cháy cao, tự dập tắt, sử dụng cho tòa nhà công cộng, khách sạn, trường học và văn phòng.
Dca: Bảo vệ cháy trung bình, phát thải hạn chế, yêu cầu cáp tối thiểu cho lắp đặt chung.
Eca: Bảo vệ cháy cơ bản, yêu cầu cáp tối thiểu cho lắp đặt chung.
Phân loại bổ sung
Khói sản sinh (s):
s1: Ít khói, lan truyền chậm.
s1a: s1 với độ nhìn thấy > 80%.
s1b: s1 với độ nhìn thấy 60-80%.
s2: Giá trị trung gian.
s3: Không phải s1 hoặc s2.
Hạt phát ra (d):
d0: Không có hạt hoặc hạt cháy.
d1: Hạt cháy trong < 10 giây.
d2: Không phải d0 hoặc d1.
Độ axit của khói (a):
a1: Độ axit thấp, dẫn điện < 2,5 ms/mm và pH > 4,3.
a2: Giá trị trung gian.
a3: Không phải a1 hoặc a2.
Tại sao LSZH không đủ?
LSZH (Low Smoke Zero Halogen) không còn đủ vì CPR áp dụng tiêu chí và quy trình thử nghiệm bổ sung. Cáp LSZH cần đáp ứng các tiêu chuẩn IEC nhưng không đảm bảo đạt tiêu chuẩn CPR.
Tầm quan trọng của Tuân thủ CPR
Giảm thiệt hại tài sản: Cáp CPR giúp giảm thiểu thiệt hại do cháy.
Yêu cầu pháp lý: Tuân thủ CPR là bắt buộc, vi phạm có thể dẫn đến hậu quả pháp lý.